The water vapour diffusion resistance value µ (pronounced "mu") indicates to what factor a material seals more than a dormant air layer of the same thickness when it comes to water vapour. The higher the µ value, the more vapour-proof the material. Understanding this dimensionless factor is essential when you're designing wall and roof assemblies that need to manage moisture effectively – whether you're working with insulation materials, membranes, or structural elements like concrete and timber.
What is the µ-value and how do you use it?
The µ-value is a dimensionless factor that compares a material's resistance to water vapour diffusion against that of still air. Air itself has a µ-value of 1. A material with µ = 50 resists vapour diffusion fifty times more than an equivalent thickness of still air. This matters on site because moisture moving through assemblies can condense on cold surfaces, leading to mold growth, rot in timber elements, and corrosion of reinforcement steel in concrete structures.
Common building materials have widely varying µ-values:
- Air: µ = 1
- Mineral wool: µ = 1
- Soft fibreboard (wood): µ ≈ 2
- Bricks, aerated concrete, plaster: µ ≈ 5
- Plasterboard: µ = 10
- Wood: µ ≈ 50
- Concrete: µ = 50–100
- Polystyrene EPS: µ ≈ 50
- PE sealing film: µ = 100,000
When you select materials for a construction detail, these values guide your choice. For instance, mineral wool and soft fibreboard remain highly permeable, while PE films form near-complete vapour barriers.
How to calculate the sd-value from the µ-value
The sd-value – water vapour diffusion equivalent air layer thickness – translates the µ-value into a practical metric measured in metres. You calculate it by multiplying the material's µ-value by its thickness in metres:
sd-value (m) = µ (dimensionless) × material thickness (m)
For example, a 20 cm thick brick wall with µ ≈ 5 has an sd-value of 5 × 0.2 m = 1 m. This means the brick wall resists vapour diffusion as much as a 1 m thick layer of still air. Similarly, an ISO-CONNECT EPDM Inside film with a thickness of 0.8 mm and µ = 300,000 yields an sd-value of 300,000 × 0.0008 m = 240 m – equivalent to a 240 m thick air layer.
The sd-value is the figure you'll typically see in product datasheets and EPD declarations, because it directly reflects the diffusion resistance of a real component at its actual installed thickness.
Material classification by sd-value according to DIN 4108-3
Section 3 of DIN 4108 categorizes materials by their sd-value, helping you select appropriate layers for interior and exterior positions in an assembly:
- Diffusion open/permeable: sd ≤ 0.5 m
- Diffusion inhibiting: 0.5 m < sd ≤ 10 m
- Diffusion retarding: 10 m < sd ≤ 100 m
- Diffusion blocking: 100 m < sd < 1500 m
- Diffusion impermeable: sd ≥ 1500 m
The preference is to have materials with a higher sd-value on the inside of a heated building than on the outside. This principle – sometimes called the "moisture gradient rule" – ensures that water vapour pressure inside the assembly can escape toward the exterior without condensing in the core. A high sd-value on the interior side hinders moisture entry, while a low sd-value on the exterior allows rapid drying.
Practical application: avoiding condensation risk on site
When you detail a wall or roof assembly, arrange layers so that vapour resistance decreases from inside to outside. For example, place a vapour control membrane (sd ≈ 20 m) on the warm side of the insulation, and use a breathable underlay (sd < 0.5 m) on the cold side. This setup prevents moisture from being trapped in the insulation, where it can reduce thermal performance and promote mold.
If you must use a vapour-tight layer on the exterior – for instance, a metal cladding – ensure an air gap or ventilation channel behind it to allow drying. Without this, even a correctly positioned interior vapour barrier may not prevent condensation if moisture enters through gaps or construction defects.
For Passivhaus and other high-performance envelopes, hygrothermal modeling (e.g., using WUFI software) can verify that your chosen material sequence remains safe across seasonal temperature and humidity swings. The modeling calculates whether condensation will form and, if so, whether it can dry out completely each year.
Takeaway for the building site
Check product datasheets for the sd-value, not just the U-value. When installing membranes, tape all joints with compatible adhesive to maintain continuity of the vapour barrier. Small gaps – around window reveals, service penetrations, or joist hangers – can short-circuit the vapour control layer and lead to hidden condensation damage. Finally, remember that diffusion is only one moisture transport mechanism; air leakage typically moves far more water vapour. Seal the airtight layer as carefully as you detail the vapour control layer, and verify with a blower-door test before close-up.